The IC200MDL743 discrete output module is a 5. 12. and 24 VDC negative logic output module that is part of the Versamax family.
It has 16 discrete outputs in a bank and an external power supply.
About the IC200MDL743
The Versamax IC200MDL743 discrete output module is a GE Fanuc 5. 12. and 24 VDC and 0.5 A rated negative logic output module.
It has 16 current-flooded discrete outputs that switch the load to the negative side of the DC supply. The module does not have any internal fuses for protection.
The output module connects directly to the controller and also allows for “hot” insertion, making installation easy.
The IC200MDL743 discrete output module communicates with the backplane through an I/O rack. The backplane provides the power needed to operate the modules.
It draws 70 mA** from the backplane. It also has an external power supply to provide the required power to the load.
The IC200MDL743 discrete output module has an on response time of 2.1 ms at 0 V DC, an off response time of 0.0 ms, and an output leakage current of 5.30 mA.
It features a compact modular design for easy and space-saving installation. This module does not provide group-to-group isolation or point-to-point isolation.
It can be used to drive a variety of output devices such as lamps, relays, and motor starters. Power wiring is recommended,
control wiring and communication signal wiring separately to minimize insulation failures and wiring errors.
There are different types of brackets, such as box brackets and spring-loaded compact brackets, to make the wiring process easy.
The IC200MDL743 discrete output module features automatic I/O addressing to maximize ease of use in PLC-based industrial control applications**.
The IC200MDL743 is a discrete signal output module from General Electric’s VersaMax family.
The device has 16 output points, each of which can be either negative logic or sinking type.
The output points on the module load-switch the negative side (also known as the return side) of a DC power supply to receive current from an electrical load.
All output load switching on the IC200MDL743 requires an external power supply. The device has two modes of operation, each with its own voltage requirements.
In the standard 12/24-volt direct current (VDC) mode, the output voltage range is 10.2 to 30 volts DC, with nominal voltages of 12 and 24 volts DC.
In 5VDC-TTL (transistor-transistor logic) mode, the output voltage is 4.75 to 5.25 volts DC, where 5 volts DC is nominal.
Each output point on the module can handle half an ampere of current in the 12/24 volt DC mode and 25 milliamps in the 5VDC-TTL mode.
Output leakage current is 0.5 mA when operating at 30 volts DC. The maximum on and off response times are 0.2 ms and 1.0 ms, respectively, for each output point.
The IC200MDL743 does not support thermal derating. The module also does not have any channel or point isolation and does not provide protection such as internal fuses.
All processing of 32-bit discrete output messages is done by the central processing unit (CPU) or network interface unit (NIU).
The IC200MDL743 is 4.3 inches wide, 2.63 inches high, and 1.956 inches deep.
Note: These specifications do not include carrier height and mating connectors.